AS-AXF-2P F300

Industrial Axial Smoke Exhaust Fans (2-Pole) – F300

AS-AXF-2P F300 axial smoke exhaust fans run with 2-pole, high-speed motors and withstand 300 °C for two hours. They evacuate smoke from car parks in the event of fire and are preferred in projects that require high airflow and pressure. The casing is made of galvanized sheet steel with round connections. The fan can be installed in-line in a duct, on a wall or on a roof, with horizontal or vertical air discharge. Aluminium impellers with 6 or 8 blades, balanced to ISO 1940-1, cover sizes from Ø315 to Ø630 mm. The direct-drive, totally enclosed fan-cooled (TEFC) 2-pole WAT motors have IP55 protection and class F insulation. The standard motor is an IE3 motor rated for F300 smoke duty (300 °C, 2 h) and for S1 and S2 duty. Versions for 400 V 3~ 50 Hz and 60 Hz supplies are available. Operating air temperature: −20 °C to +300 °C. Standards: IEC 60335-2-80, ISO 1940-1.
AS-AXF-2P F300
AS-AXF-2P F300 — Dimensions

Models (7)· 50 Hz

ModelDiameter [mm]Max. airflow [m³/h]Max. pressure [Pa]Motor [kW]Speed [min⁻¹]Lp 1 m [dB(A)]Datasheet
AS-AXF-2P F300 315-6-453155,342*467*0.75IE3 F3002,90387 Datasheet
AS-AXF-2P F300 355-6-453557,573*551*1.10IE3 F3002,90889 Datasheet
AS-AXF-2P F300 400-6-4540010,596*560*3.00IE3 F3002,93493 Datasheet
AS-AXF-2P F300 450-6-4545015,597*944*4.00IE3 F3002,91796 Datasheet
AS-AXF-2P F300 500-6-4550020,326*981*5.50IE3 F3002,92798 Datasheet
AS-AXF-2P F300 560-6-4556032,602*2,802*7.50IE3 F3002,934103 Datasheet
AS-AXF-2P F300 630-8-4563036,572*1,486*15.00IE3 F3002,967104 Datasheet

* Curve scaled to the motor speed with the fan laws (Q∝n, p∝n²) — estimate.