A05 · Car park & smoke extract fans
AS-AXF F300
Industrial Axial Smoke Exhaust Fans – F300
AS-AXF F300 axial smoke exhaust fans withstand 300 °C for two hours. Used together with jet fans, they evacuate smoke from car parks in the event of fire.
The casing is made of galvanized sheet steel with round connections. The fan can be installed in-line in a duct, on a wall or on a roof, with horizontal or vertical air discharge. Aluminium impellers with 5, 6, 8 or 12 blades, balanced to ISO 1940-1, cover sizes from Ø450 to Ø1,400 mm.
The direct-drive, 4-pole WAT motors have TEAO cooling, IP55 protection and class F insulation. The standard motor is an IE3 motor (IE4 on the largest Ø1,400 model) rated for F300 smoke duty (300 °C, 2 h) and for S1 and S2 duty. Versions for 400 V 3~ 50 Hz and 60 Hz supplies are available. Operating air temperature: −20 °C to +300 °C. Standards: IEC 60335-2-80, ISO 1940-1.


Models (20)· 50 Hz
| Model | Diameter [mm] | Max. airflow [m³/h] | Max. pressure [Pa] | Motor [kW] | Speed [min⁻¹] | Lp 1 m [dB(A)] | Datasheet |
|---|---|---|---|---|---|---|---|
| AS-AXF F300 450-5-25 | 450 | 4,180 | 253 | 0.55IE3 F300 | 1,455 | 69 | Datasheet |
| AS-AXF F300 500-5-25 | 500 | 5,845 | 305 | 0.55IE3 F300 | 1,455 | 72 | Datasheet |
| AS-AXF F300 560-5-25 | 560 | 8,105* | 354* | 0.75IE3 F300 | 1,458 | 75 | Datasheet |
| AS-AXF F300 630-5-30 | 630 | 13,324* | 442* | 1.10IE3 F300 | 1,448 | 80 | Datasheet |
| AS-AXF F300 710-5-30 | 710 | 18,949* | 508* | 1.50IE3 F300 | 1,452 | 83 | Datasheet |
| AS-AXF F300 800-5-30 | 800 | 25,560 | 577 | 2.20IE3 F300 | 1,458 | 85 | Datasheet |
| AS-AXF F300 800-5-35 | 800 | 30,940 | 634 | 3.00IE3 F300 | 1,457 | 89 | Datasheet |
| AS-AXF F300 900-5-35 | 900 | 39,250 | 664 | 5.50IE3 F300 | 1,473 | 90 | Datasheet |
| AS-AXF F300 900-5-40 | 900 | 44,635 | 694 | 5.50IE3 F300 | 1,473 | 93 | Datasheet |
| AS-AXF F300 900-8-40 | 900 | 47,027* | 982* | 15.00IE3 F300 | 1,480 | 94 | Datasheet |
| AS-AXF F300 1000-5-40 | 1,000 | 54,570 | 691 | 7.50IE3 F300 | 1,474 | 94 | Datasheet |
| AS-AXF F300 1000-8-40 | 1,000 | 63,489* | 1,121* | 18.50IE3 F300 | 1,485 | 97 | Datasheet |
| AS-AXF F300 1000-8-45 | 1,000 | 70,444* | 1,161* | 22.00IE3 F300 | 1,487 | 99 | Datasheet |
| AS-AXF F300 1120-12-50 | 1,120 | 111,881* | 1,324* | 45.00IE3 F300 | 1,485 | 110 | Datasheet |
| AS-AXF F300 1120-8-40 | 1,120 | 87,382* | 1,323* | 30.00IE3 F300 | 1,484 | 100 | Datasheet |
| AS-AXF F300 1120-8-45 | 1,120 | 95,918* | 1,363* | 30.00IE3 F300 | 1,484 | 102 | Datasheet |
| AS-AXF F300 1400-6-24 | 1,400 | 101,534* | 1,608* | 30.00IE3 F300 | 1,484 | 90 | Datasheet |
| AS-AXF F300 1400-6-28 | 1,400 | 124,372* | 1,839* | 45.00IE3 F300 | 1,485 | 94 | Datasheet |
| AS-AXF F300 1400-6-30 | 1,400 | 135,346* | 1,971* | 55.00IE3 F300 | 1,492 | 96 | Datasheet |
| AS-AXF F300 1400-6-34 | 1,400 | 157,593* | 2,141* | 75.00IE4 F300 | 1,492 | 98 | Datasheet |
* Curve scaled to the motor speed with the fan laws (Q∝n, p∝n²) — estimate.
Models (18)· 60 Hz
Catalogue page
Printable A4 catalogue page, made from the AEROMIS product database.