A03 · Car park & smoke extract fans

AS-RJET F300

Industrial Backward-Curved Centrifugal Jet Fans – F300

AS-RJET F300 jet fans are designed for car park ventilation. Pushing air through the open space instead of carrying it through ducts, they avoid the friction losses of ducted systems. Their low profile suits car parks with limited headroom; they do not obstruct other services, are easy to install and are suitable for automation. The galvanized sheet steel casing is installed without ducts and discharges air horizontally. The backward-curved centrifugal impeller is made of aluminium and balanced to ISO 1940-1; sizes range from Ø560 to Ø630 mm. Thrust ranges from 50 to 90 N. Direct drive is provided by two-speed 4/8-pole Dahlander WAT motors with TEAO cooling, IP55 protection, class F insulation and efficiency class IE3. They are rated for 300 °C for two hours (F300) and for S1 and S2 duty. Versions for 400 V 3~ 50 Hz and 60 Hz supplies are available. Operating air temperature: −20 °C to +300 °C. Standards: IEC 60335-2-80, ISO 1940-1.
AS-RJET F300
AS-RJET F300 — Dimensions

Models (3)· 50 Hz

ModelDiameter [mm]Max. airflow [m³/h]Thrust [N]Motor [kW]Speed [min⁻¹]Lp 1 m [dB(A)]Datasheet
AS-RJET F300 505605,760*501.202D F3001,43054 Datasheet
AS-RJET F300 706307,009*702.802D F3001,43858 Datasheet
AS-RJET F300 906307,641*902.802D F3001,43862 Datasheet

* Curve scaled to the motor speed with the fan laws (Q∝n, p∝n²) — estimate.

Catalogue page

Printable A4 catalogue page, made from the AEROMIS product database.

↓ Catalogue page (PDF)
AS-RJET F300 — Catalogue page 1AS-RJET F300 — Catalogue page 2